Series 735PV
Plastic Tee Type Impeller Flow Sensor
880096-0001-EN (January 2013)
Rev. 3 Installation & Operation Manual
Sections of this document marked with or must be consulted for safe use of the product.
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - Series 735PV

Series 735PVPlastic Tee Type Impeller Flow Sensor880096-0001-EN (January 2013)Rev. 3 Installation & Operation ManualSections of this document mark

Page 2 - CONTENTS

SPECIFICATIONSWetted Materials (except tees) See "Ordering Matrix" in Technical Brief for material specifications.MaterialsTee PVC Type 1, w

Page 3 - ELECTRONIC TYPES

INTENTIONAL BLANK PAGEInstallation & Operation ManualPage 11 January 2013

Page 4 - MECHANICAL INSTALLATION

www.badgermeter.comData Industrial is a registered trademark of Badger Meter, Inc. Other trademarks appearing in this document are the property of th

Page 5 - ELECTRICAL INSTALLATION

CONTENTSINTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3ELECTRONIC TYPE

Page 6 - INSTALLATION INFORMATION

INTRODUCTIONUsed in conjunction with any Badger Meter flow monitor or endpoint, Badger Meter non-magnetic Impeller flow sensors provide an accurate re

Page 7 - Additional Information

MECHANICAL INSTALLATION Depressurize and vent piping system prior to any installation or maintenance of the flow sensor.GeneralThe accuracy of flow me

Page 8 - CALIBRATION

ELECTRICAL INSTALLATIONDisconnect power from flow sensor source and/or receiving device prior to any installation or maintenance of the system.Flow s

Page 9 - DIMENSIONS

INSTALLATION INFORMATIONDepressurize and vent piping system prior to any installation or maintenance of the flow sensor.Disconnect power from flow sen

Page 10 - SPECIFICATIONS

4. Insert the sensor into the tee, carefully lining up the locating hole in the sensor with the locating pin in the tee.5. Install and HAND TIGHTEN

Page 11 - INTENTIONAL BLANK PAGE

CALIBRATIONBadger Meter Impeller sensors use unique K and offset numbers for calibration. These numbers are derived from calibration runs using NIST t

Page 12

DIMENSIONSA Soc Size, NPSB C/L to TopL LBSP1/2" [Ø.840"] 3.85" 3.06" 6.086"3/4" [Ø1.050"] 3.85" 3.31" 6.7