Badger-meter 340 BN/MB Btu Energy Transmitter Manuel d'utilisateur Page 26

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 28
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 25
SPECIFICATIONS
POWER
Power supply options:
12…35V DC
12…24V AC
Current draw:
115 mA max. @ 12V DC
FLOW SENSOR INPUT
Pulse type sensors
Signal amplitude:
2.5V DC threshold
Signal limits:
Vin < 12V (DC or AC peak)
Frequency:
4…10000 Hz
Pull-up:
2k  to 15V DC
Sine wave sensors
Signal amplitude:
30 mV p-p threshold
Signal limits:
Vin < 12V (DC or AC peak)
Frequency:
4…10000 Hz
Excitation voltage 3-wire sensors
7.0V DC to 11.4 V DC 500  source impedance
TEMPERATURE SENSOR INPUT
2 required:
10k Ω thermistor, 2 wire, type II,10k Ω, @ 25°C
100 Ω RTD, Platinum three wire,
1000 Ω RTD, Platinum, two or three wire
RTDs follow IEC 751 DIN Curve
PULSE OUTPUT
Pulse width:
Programmable 10 ms to 5 sec. in 50 ms steps
Pulse frequency:
Max of 10 Hz at 50 ms pulse width programmable to scaling
requirements of connected device (Flow or Energy)
Opto-isolated solid state switch
Operating voltage range:
0 to ± 45V (DC or AC peak)
Closed (on) state:
Load Current - 700 mA max.
over operating temperature range
Open (off) state - leakage @ 70ºC
<1µA @ 45V (DC or AC peak)
OPERATING TEMPERATURE
0…70° C
32…158° F
Storage Temperature
– 40…85° C
– 40…185° F
WEIGHT
4.8 oz with connector headers installed
SENSOR CALIBRATION
Badger Meter –
Use K and Offset provided in sensor owner’s manual
Other sensors –
Check with factory
UNITS OF MEASURE
Flow measurement
Rate:
gpm, gph, l/sec, l/min, l/hr, ft
3
/sec, ft
3
/min,
ft
3
/hr, m
3
/sec, m
3
/min, m
3
/hr
Total:
gallons, liters, cubic feet, cubic meters
Energy measurement
Rate:
kBtu/min, kBtu/hr, kW, MW, hp, tons
Total:
Btu, kBtu, MBtu, kWh, MWh, kJ, MJ
Temperature Units:
Fahrenheit, Centigrade
PROGRAMMING
Requires PC or laptop running Windows® XP, Vista or
Windows 7
Data Industrial 340 BN/MB Programming Kit A301-20
containing software and programming cable
Data Industrial® 340 BN/MB BTU Energy Transmitter
Page 26 July 2012
Vue de la page 25
1 2 ... 21 22 23 24 25 26 27 28

Commentaires sur ces manuels